Piusi Ocio Tank Level Gauge
Piusi Ocio Tank Level Gauge 230vAC Level gauge
Reading Type: 0-100%/mm/inches/litres/gal
Tank Height (mm) - 600-4000
Capillary Length (m) - 10
Capillary Type - 6 x 4 Rilsan PA12
Balance Chamber Fitting: 1/2" M BSP
Max Working Temperature: -20ºc/+50ºc
Fluids: Diesel, water, windscreen fluid, Adblue and oil (See Options)
Accuracy: ±1%
Enclosure Rating: IP55
Two Relay outputs for high low alarms
Fluid Options:
- Diesel, Water, Windscreen fluid with Brass Chamber
- Adblue / Urea with Stainless Seel Chamber
- Special kit for Oils with Brass Chamber
Optional 4-20mA output
Optional PC Software
Continuous tank level monitoring.
OCIO detects the static pressure generated by the fluid height by means of a tube inserted into the tank and displays the fluid level or volume.
The system consists of:
- A tube for detecting static pressure: The tube end is inserted from the top of the tank and lowered down into the liquid until it touches the bottom.
- A control unit for displaying the level and managing the system. The unit is equipped with intuitive software and permits the connection of two alarms / devices
The software is used to:
- Set the tank type and dimensions
- Define alarm levels
- Define indication level
- Define measurement unit
- Calibrate the instrument