DN25 Coriolis Mass Flow Meter
SKU: CG-25Max Flow rate 200 Kg/min (20:1 Turndown)
Liquid Accuracy +/- 0.1% (See options)
Gas Accuracy +/- 0.5%
Repeatability +/- 0.05%
Tube Material 316 Stainless Steel
40 Bar Max W.P (Subject to connections)
DN25 Flanges PN40 (See options)
Process Temp -70 to 160 Deg. C (See Options)
Remote Display 24V DC or 85~265V AC, 50/60 Hz
Cable Length 5m (See options)
4-20mA, pulse, Modbus RTU RS485 (HART optional)
ATEX (Flow Sensor) - II 2G Ex db IIC T6...T1 Gb
ATEX (Transmitter) - II 2G Ex db [ib] IIC T6...T1 Gb
Description
Max Flow rate 200 kg/min (20:1 Turndown)
Liquid Accuracy +/- 0.1% (See options)
Gas Accuracy +/- 0.5%
Repeatability +/- 0.05%
Tube Material 316 Stainless Steel
40 Bar Max W.P (Subject to connections)
DN25 Flanges PN40 (See options)
Process Temp -70 to 160 Deg. C (See Options)
Remote Display 24V DC or 85~265V AC, 50/60 Hz
Atmospheric Temp -30 to 60 Deg. C
IP67 Ingress Protection Rated
Cable Length 5m (See options)
4-20mA, pulse ,Modbus RTU RS485 (HART optional)
ATEX (Flow Sensor) - II 2G Ex db IIC T6...T1 Gb
ATEX (Transmitter) - II 2G Ex db [ib] IIC T6...T1 Gb
Specification
CG-25 Coriolis Mass Flow Meter
Max Flow rate 200 Kg/min (20:1 Turndown)
Liquid Accuracy +/- 0.1% (See options)
Gas Accuracy +/- 0.5%
Repeatability +/- 0.05%
Tube Material 316 Stainless Steel
40 Bar Max W.P (Subject to connections)
DN25 Flanges PN40 (See options)
Process Temp -70 to 160 Deg. C (See Options)
Remote Display 24V DC or 85~265V AC, 50/60 Hz
Atmospheric Temp -30 to 60 Deg. C
IP67 Ingress Protection Rated
Cable Length 5m (See options)
4-20mA, pulse ,Modbus RTU RS485 (HART optional)
ATEX (Flow Sensor) - II 2G Ex db IIC T6...T1 Gb
ATEX (Transmitter) - II 2G Ex db [ib] IIC T6...T1 Gb
Temp. Accuracy ±1.0 oC ±0.5 of reading
Density Accuracy ±0.001 g/cm3 (liquid)
Zero Stability 0.01 kg/h
Repeatability ±0.05%
Volume Calculation
This Mass flow meter measures mass directly, but it can also show volume. There are 2 options for volume calculation, by fixed & real-time density. Fixed density is the one you input, which does not change and the real-time density is the one the meter measures, which changes when the flow, environment etc. changes
Units of Measurement
Mass Total: G, kg, T, St, lt, lb
Volume Total: m3 , L, ft3 , barrels, UKgal, USgal
Mass Flow: lt/day, lt/hour, st/day, st/hour, st/min, lb/day, lb/hour, lb/min, lb/s, T/day, T/hour, T/min, kg/day, kg/hour, kg/min, kg/s, g/hour, g/min, Special
Volume Flow: ft3 /h, ft3 /min, USgal/day, L/hour, UKgal/h, USgal/h, Bar/day, Bar/h, m3 /hour, m3 /s, m3 /min, Special
Temp: 0C, 0 F, K, 0R
Density: g/cm3 , st/yd3 , lb/in3 , g/L, kg/L, g/mL, lb/ft3 , lb/gal, kg/m3